Conext Automatic Generator Start Installation

Installing the Xantrex XW Automatic Generator Start
975-0307-01-01 2–15
Type 6
Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact.
Figure 2-12 Type 6 Connection Diagram
Table 2-10 Type 6 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
10 s
Preheat to crank delay
1 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
XW AGS Harness Wires Generator Wires
18
17
16
15
13
12
14
Relay 2
Relay 1
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
PREHEAT
STOP
START
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
START
PREHEAT
STOP