Conext Automatic Generator Start Installation

Installation
2–16 975-0307-01-01
Type 7
Type 7 will work with both two-wire and three-wire run mode configurations
that require a preheat signal before cranking. This Gen Type setting is
suitable for generators with an automatic engine cranking control system
(two-wire) and generators that require that the Xantrex XW AGS control their
starter separately (three-wire).
Figure 2-13 Type 7 Connection Diagram (two-wire)
Figure 2-14 Type 7 Connection Diagram (three-wire)
Table 2-11 Type 7 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
Run
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
20 s
Preheat to crank delay
1 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
XW AGS Harness Wires Generator Wires
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
XW AGS Harness Wires Generator Wires
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
START
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
START