Conext Automatic Generator Start Installation

Installation
2–18 975-0307-01-01
Type 9
Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3.
Figure 2-17 Type 9 Connection Diagram
Table 2-13 Type 9 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
StartStop
Relay 3 mode
Shutdown Bypass
Gen Run signal hold
time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
5 s
Start tries
3
XW AGS Harness Wires Generator Wires
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP
START
GENERATOR BATTERY NEGATIVE (–)
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
START
STOP
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +