Conext Automatic Generator Start Installation

Installing the Xantrex XW Automatic Generator Start
975-0307-01-01 2–19
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.
Figure 2-18 Type 10 Connection Diagram
Table 2-14 Type 10 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
StartStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
STOP
START
XW AGS Harness Wires Generator Wires
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
START
STOP