Conext Automatic Generator Start Installation

The Xantrex XW Automatic Generator Start Menu
975-0307-01-01 3–9
QT End
Full name Quiet Time End
Purpose “QT End” is a changeable setting that defines the end of quiet time.
This setting also requires a setting for “QT Begin”.
Dependencies “QT End” functions only if the Xantrex XW AGS is in Automatic mode.
This setting requires “QT En” be set to [Enabled] and also requires a
setting for “QT Begin”.
Ensure the clock on the Xantrex XW System Control Panel is set to the
correct local time.
Value Description
12:00AM to 11:59PM
(12-hour clock)
00:00 to 23:59
(24-hour clock)
At the time set for
“QT End” the Xantrex XW
AGS will be able to automatically start the
generator again. If a start trigger has occurred
during quiet time and is still active, the
generator will start immediately after quiet time
ends.