Conext Automatic Generator Start Installation

The Xantrex XW Automatic Generator Start Menu
975-0307-01-01 3–17
Stop Float
Full name Stop at Float Charge Stage
Purpose The “Stop Float” trigger allows the Xantrex XW AGS to stop the generator
when the inverter/charger has recharged the batteries to the Float stage.
Considerations “Stop Float” or “Stop Absorb” would typically be used if the generator
was started due to a low-battery voltage setting.
“Stop Float” is the recommended setting if it is desired that the generator
charge the batteries completely. This will result in somewhat longer run
times. However, if the generator is the primary charging source, charging
them to the Float stage every time will provide longer battery life.
For more information on battery charging, see the Xantrex XW Inverter/
Charger Operator’s Guide.
Values Default
Disabled, Enabled Disabled