Conext Automatic Generator Start Installation

The Xantrex XW Automatic Generator Start Menu
975-0307-01-01 3–19
Stop V
Full name Stopping Battery Voltage
Purpose The “Stop V” trigger enables the Xantrex XW AGS to stop the generator
whenever the battery voltage reaches a pre-set DC voltage. Whenever
the generator starts automatically based on the Starting Battery Voltage,
it will shut off once the Stopping Battery Voltage has been reached.
Dependencies The “Stop V” trigger requires the Xantrex XW AGS to be in Automatic
mode and needs a parameter to be set for one of the Start DCV triggers.
Considerations The “Stop V” setting is most useful when you want the inverter/charger to
give the batteries a quick, basic charge. If using this mode, it is
recommended to run a complete charge or equalize cycle once in a
while to restore the battery. To give the batteries a more complete,
consistent charge, use the “Stop Float” setting. This will result in longer
generator run times.
If “Stop V” is set too high, the generator may run for too long.
If “Stop V” is set too low, the Xantrex XW AGS will stop the generator
before the inverter/charger has charged the batteries.
If “Stop Float” or “Stop Absorb” have been enabled, the Xantrex XW AGS
will stop the generator if the Float or Absorption stages of the battery
charging have begun.
Actual battery voltage can be monitored from the Xantrex XW System
Home screen on the Xantrex XW System Control Panel.
For more information on battery charging, see the Xantrex XW Inverter/
Charger Operator’s Guide.
Values Default
Disabled, 14.0 V to 65.0 V
(increments of 0.1 V)
Disabled