Conext Automatic Generator Start Installation

Configuration
3–20 975-0307-01-01
Temp1
Full name Thermostat 1
Purpose The “Temp1” trigger enables the generator to start in response to a
signal from a thermostat. With “Temp1” set to [Enabled], the Xantrex XW
AGS will start the generator to help power the item controlled by that
thermostat.
When to use Enable “Temp1” if a thermostat is available that controls a component
that has a high-power requirement such as a furnace or an air
conditioning system.
Considerations If “Temp1” is enabled, the generator will start in response to a signal from
the thermostat. Everything related to setting the thermostat must be done
on the thermostat. For example: setting the temperature at which the
furnace or air conditioning system comes on must be done on the
thermostat. There are no thermostat temperature settings on the Xantrex
XW AGS or the Xantrex XW System Control Panel.
If “Temp1” is disabled, the component connected to that thermostat will
require that the generator be started manually in order for that
component to have power. Otherwise, the component will need to be
connected to another AC input source.
Temp2
Full name Thermostat 2
Purpose “Temp2” is intended to be used when the Xantrex XW AGS is connected
to a second thermostat. All information and procedures for “Temp1” also
apply for “Temp2”.
Values Default
Disabled, Enabled Disabled
Values Default
Disabled, Enabled Disabled