Conext Automatic Generator Start Installation

Configuration
3–28 975-0307-01-01
Exercise Dur
Full name Exercise Duration (in minutes)
Purpose “Exercise Dur” sets how long the generator will run when it is exercised.
Dependencies The “Exercise Dur” trigger requires that any parameter other than “0” be
set in “Exercise Per” and a time of day be set in the “Exercise Time”
trigger.
Exercise Time
Purpose “Exercise Time” sets the time of day that the Xantrex XW AGS exercises
the generator.
The “Exercise Time” trigger requires that any parameter other than “0” be
set in “Exercise Per” and a value be set in the “Exercise Dur” trigger.
Considerations If the Exercise Time is set, the generator will start at that time after being
inactive for the Exercise Period.
If the Exercise Time occurs during Quiet Time, the generator will start
when Quiet Time is over and run for the full amount of time set for
“Exercise Dur”.
Values Default
1min to 250min 30min
Important: Ensure that the Exercise Duration is not set for longer than
the “Max Run Time” setting. Attempting to do so will generate a warning
on the System Control Panel.
Important: Consult the generator manual or a service representative
from the generator’s manufacturer for the recommended exercise
duration.
Values Default
12:00AM to 11:50PM (12-hour clock)
00:00 to 23:50 (24-hour clock)
(increments of 10 minutes)
9:00AM