Conext Automatic Generator Start Installation

Configuration
3–30 975-0307-01-01
Considerations This setting is automatically configured when a “Gen Type” is selected
for the generator. Manually change this setting only on the advice of the
generator manufacturer or authorized service personnel.
If the installation is made without a B+ connection, it might be necessary
to adjust the Gen Run Hold Time for the Xantrex XW AGS to succesfully
start the generator. When the B+ signal is not connected, the Xantrex XW
AGS requests generator status from the Inverter/Charger, which might
take longer that if the B+ signal was connected.
Crank Delay
Purpose “Crank Delay” specifies the delay time from when the preheat relay is de-
energized to when the Start Relay is energized (and cranking the starter
motor). This is also referred to as the preheat-to-crank delay.
Considerations This setting is automatically configured when a “Gen Type” is selected
for the generator. Manually change this setting only on the advice of the
generator manufacturer or authorized service personnel.
Crank Time
Purpose “Crank Time” specifies the maximum length of time the Start relay is
engaged (and cranking the starter motor) for the first attempt to start the
generator.
Considerations This setting is automatically configured when a “Gen Type” is selected
for the generator. Manually change this setting only on the advice of the
generator manufacturer or authorized service personnel.
Values Default
0s to 60s 0s
Values Default
0s to 250s (increments of 1s) 30s