Conext Automatic Generator Start Installation

Configuration
3–38 975-0307-01-01
Generator Menu Items:
“Starter Cool Down” 1s to 250s (increments of 1s) 60s
“Gen Cool Down” 0s to 600 s (increments of 1s) 30s
“Gen Spin Down” 1s to 900s (increments of 1s) 3s
“Max Run Time” 0hours–24 hours 8hours
“Exercise Per 0days (Off)–250days 21days
“Exercise Dur” 1min–250min 30min
“Exercise Time 12:00AM–11:50PM (12-hour clock)
00:00–23:50 (24-hour clock)
9:00AM (12-hour clock)
9:00 (24-hour clock)
“Relay3” Preheat, WrmupCoolDn, Preheat
SDByp, NotUsed
NotUsed
“Gen Run Hold
Time”
0s to 20s (increments of 1s) 0.5s
“Crank Delay” 0s to 60s (increments of 1s) 0s
“Crank Time” 0s to 250s (increments of 1s) 30s
“Crank Retry Time” 0s to 250s (increments of 1s) 40s
“Preheat Time” 0s to 250s (increments of 1s) 0s
“Gen Start Tries” 1 to 10 3
Multi-Unit Configuration:
“Dev Name” 1-15 characters Xantrex XW AGS
“Dev Number” 00 to 31 00
Connections:
“DC Conn” None, HouseBatt1 to 6,
StartBatt1 to 6
HouseBatt1
“AC In” None, Grid1to 10, Gen1 to 10 Grid1
“AC Out” None, ACLoad1 to 10 ACLoad1
“Generator” Gen1 to 10 Gen1
Table 3-24 Generator Configuration Settings, Values, Defaults, and User Settings
Setting Values Default
User
Setting