Using Quiet Time
Use the Quiet Time feature to ensure that the Xantrex XW AGS will not
start the generator during the night or during times that conflict with local
noise restrictions.
Using Quiet Time involves three steps.
1. “QT En” must be set to [Enabled]. The default setting is [Enabled].
2. “QT Begin” must have an appropriate time set for Quiet Time to start
on schedule. The default setting for “QT Begin” is [9:00 PM] or 21:00
if using a 24-hour clock.
3. “QT End” must have an appropriate time set for Quiet Time to stop
on schedule. The default setting for “QT End” is [8:00 AM] or 8:00 on
the 24-hour clock.
For more information about Quiet Time settings, see “QT En” on page 3–
7, “QT Begin” on page 3–8, and “QT End” on page 3–9.
To enable Quiet Time:
1. On the Auto Gen Start menu, use the arrow buttons to highlight “QT
En”.
2. Press Enter.
3. Use the arrow buttons to select [Enabled].
4. Press Enter.
To set the beginning of Quiet Time:
1. On the Auto Gen Start menu, use the arrow buttons to highlight “QT
Begin”, then press Enter.
2. Use the arrow buttons to select the hour, then press Enter.
3. Use the arrow buttons to select the minutes, then press Enter.
If the 24-hour clock is being used, go to step 5.
4. Use the arrow buttons to select AM or PM, then press Enter.
5. Press Exit twice to return to the System Home screen.
Figure 4-35 Using the Quiet Time Feature
Xantrex XW System
Home Screen
Select Device Menu
Xantrex XW AGS
Menu
Set Quiet Time
settings