Conext Automatic Generator Start Installation

Modes of Operation
975-0307-01-01 4–5
To set the end of Quiet Time:
1. On the Auto Gen Start menu, use the arrow buttons to highlight “QT
End”, then press Enter.
2. Use the arrow buttons to select the hour, then press Enter.
3. Use the arrow buttons to select the minute, then press Enter.
If the 24-hour clock is being used, go to step 5.
4. Use the arrow buttons to select AM or PM, then press Enter.
5. Press Exit twice to return to the System screen.
Modes of Operation
The Xantrex XW AGS, like all other Xantrex Xanbus-enabled devices,
supports two modes, Operating and Standby. The Xantrex XW AGS
mode of operation must be set to Standby before selecting a Generator
Type. Selecting Standby stops the generator (if it is running).
While in Standby, the Xantrex XW AGS “listens” to and reports its status
to the network. However, it will not start the generator manually or
automatically while in Standby.
If the Xantrex XW AGS is powered off while in Standby, it will be in
Standby when it is powered on again.
The Xantrex XW AGS can also be put in Standby using the system mode
option under system settings. However, note that selecting Standby from
system settings affects the behavior of the entire Xantrex XW system.
System mode Standby puts every Xantrex Xanbus-enabled device in
Xantrex XW Power System into Standby.
Important: If Xantrex XW AGS Fault 201 “Unable to stop gen.” is active,
the Xantrex XW AGS cannot be put into Standby. Before Standby can be
established, the generator must be stopped by its external switch and
the fault must be cleared.