Conext Automatic Generator Start Installation

Troubleshooting
5–4 975-0307-01-01
W203 Manual Off:
Max
generator run
time reached.
Reset
GenMode.
No The generator has
run for its maximum
allowable time. The
Xantrex XW AGS has
stopped the
generator and
changed the
GenMode to
[ManualOff].
Acknowledge the warning.
Return the Xantrex XW AGS to
the desired GenMode
[Automatic or ManualOn].
Ensure generator has fuel and is
supplying the required power for
battery charging and loads.
W205 Generator
started by its
switch. Use
its switch to
stop.
Yes The generator was
started, but not by
the Xantrex XW
AGS.
Check your generator. Stop it
using the switch or control panel
on the generator.
W206 Mismatched
triggers.
Enable stop
trigger or
disable start
trigger.
No You have set a start
trigger, but not a
corresponding stop
trigger.
Acknowledge warning and set a
stop trigger.
W207 Mismatched
triggers.
Enable start
trigger or
disable stop
trigger.
No You have set a stop
trigger, but not a
corresponding start
trigger.
Acknowledge warning and set a
start trigger.
W208 Automatic
start and stop
triggers not
enabled.
Configure
triggers.
No You are attempting
to enter Automatic
Mode without setting
triggers.
Acknowledge warning and set
start and stop triggers.
Table 5-25 Xantrex XW AGS Warning Messages(Continued)
Warning
Number Message
Self-
clearing? Cause Action