Conext Automatic Generator Start Installation

Warning Messages
975-0307-01-01 5–5
W209 Gen external
stop. Start
gen via its
control panel.
Yes The generator has
stopped, but not by
the Xantrex XW
AGS. The generator
may have run out of
gas, or may have
been shut off by a
switch on the
generator.
Check the generators fuel level
and mechanical condition, then
start the generator manually
(using the switch or control
panel on the generator) to clear
the warning.
W250 The selected
value failed to
change.
Try again.
No You have tried to
change the Gen
Type without putting
the system into
Standby first.
Put the system into Standby,
change the Gen Type, then
return the system to Operating
mode.
You have tried to set
the “Exercise Dur”
for longer than “Max
Run Time,” or “Max
Run Time” for less
than “Exercise Dur.”
Ensure that “Max Run Time” is
set for longer than “Exercise
Dur.”
W500 Network
connection
lost. Check
connections.
Yes The Xantrex XW
AGS has lost
communications
with the network
because of a faulty
connection or
electronic signal
disruption.
Check connection between the
Xantrex XW AGS and the
network.
W501 Xantrex XW
AGS has
fixed memory
problem and
restored
default
settings.
No The Xantrex XW
AGS encountered
an internal memory
problem upon
startup. To remain
operational, the
Xantrex XW AGS
restored its default
settings.
Acknowledge the warning and
reset configurable settings if
necessary.
Table 5-25 Xantrex XW AGS Warning Messages(Continued)
Warning
Number Message
Self-
clearing? Cause Action