P(f) Frequency-Watt Function
When the Conext XW Pro is in Grid Support mode and P(f) function is enabled:
n The Conext XW Pro dynamically increases the active power injected into the grid
from the pre-disturbance level when AC frequency trends lower than f2, following the
P1P2 segment in the figure below.
n The Conext XW Pro dynamically curtails active power injected into utility grid from
the pre-disturbance level when AC frequency trends higher than f52, following the
P5P6 segment in the figure below.
The P(f) function is disabled by default.
Figure 53P(f) Frequency-Watt Function
P – The Conext XW Pro output active power in percentage of nominal rated active power
Sn [%Sn].
f - Utility grid frequency in Hz
Parameter
Frequency [Hz] Active Power [%Pn]
Default Range Default Range
Point P1 58 56 to 59 100 0 to 100
Point P2 59.96 59 to 59.96 0 0
Point P3 59.98 59 to 60 0 0
Point P4 60.02 60 to 61 0 0
Point P5 60.04 60.04 to 61 0 0
Point P6 62 61 to 64 -100 -100 to 0
Table 57IEEE1547-2003 P(f) Frequency-Watt function default and adjustability
range settings – 60 Hz
Conext XW Pro Owner's Guide Specifications