P(V) Volt-Watt Function
When the Conext XW Pro is in Grid Support mode and P(V) function is enabled:
n The Conext XW Pro dynamically increases the active power injected into the utility
grid from the pre-disturbance level when AC voltage trends lower than V2, following
the P1P2 segment in the figure below.
n The Conext XW Pro dynamically curtails active power injected into the utility grid
from the pre-disturbance level when AC voltage trends higher than V5, following
P5P6 segment in the figure below.
The P(V) function is disabled by default.
Figure 60P(V) Volt-Watt Function
P The Conext XW Pro output active power in percentage of nominal rated active power
Pn.
V - Utility grid voltage in percentage) of nominal voltage Vn [%Vn]
For example, V1 = 90% means V1=216 V for Vn = 240 V nominal grid.
Parameter
Voltage [% Vn] Active Power [%Pn]
Default Range Default Range
Point P1 90 85 to 98 100 0 to 100
Point P2 94 90 to 98 0 0
Point P3 95 90 to 100 0 0
Point P4 105 100 to 110 0 0
Point P5 106 102 to 110 0 0
Point P6 110 102 to 115 -100 -100 to 0
Table 72PREPA P(V) Volt-Watt function default and adjustability range
settings
Specifications Conext XW Pro Owner's Guide