Conext XW PRO 6848 6,800W 48V Installation
Table Of Contents
- Safety Information
- Label Symbols
- Product Labels
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Monitoring Operation
- External Monitoring Control
- Configuration
- Troubleshooting
- Specifications
- Electrical Specifications
- Mechanical Specifications
- Regulatory Approvals
- Grid Support Utility Interactive Functions
- California Rule 21: Smart Inverter Grid-Support Utility Interactive Functions
- Hawaiian Electric Company (HECO) Rule No. 14: Smart Inverter Grid-Support Uti...
- IEEE 1547-2003 Standard for Interconnecting Distributed Resources with Electr...
- Puerto Rico Energy Power Authority (PREPA) Technical Requirements for Interco...
- Defaults
Item Description
Equalize Now
Set to Enable to force an equalization process.
Equalize Voltage
Set Point
Selects the equalization voltage for a Custom battery type. Consult
your battery manufacturer for equalization voltage setting.
Bulk/Boost
Voltage Set Point
Sets the bulk voltage for a custom battery type. When set above the
absorption voltage set point, this value becomes the reference for
boost voltage.
Absorption
Voltage Set Point
Sets the absorption voltage for a custom battery type.
Float Voltage Set
Point
Sets the float voltage for a custom battery type.
Battery
Temperature
Coefficient
Battery temperature compensation for a custom battery type. This
setting is the reference that the BTS uses to adjust the charging
voltage when the temperature is above or below 25°C (77 °F).
The following voltage thresholds are not temperature compensated:
n Grid Support entry voltage
n Grid Support exit voltage
n Low Battery Cut-Out trigger voltage
n Low Battery Cut-Out condition clear voltage
The following battery voltage set points are temperature
compensated:
n Float exit voltage
n Bulk exit voltage
n Float and Gassing voltages used in Constant Voltage exit
criteria
n Recharge Volts
n Charge Control target voltage
Max Discharge
Current
Each Lithium Ion battery has an internal contactor and over load
protection which is based on maximum current. If exceeded, the
contactor may open, resulting in complete isolation of the battery
pack, thus removing power to the Conext XW Pro. In this case the
Xanbus communication as well as devices powered from the
Conext XW Pro could become unusable. When the Conext XW Pro
current draw exceeds the set value for a period defined in Max
Discharge Time Interval, the Conext XW Pro disables INV
output.
Max Discharge
Time Interval
Allows the Conext XW Pro current in Invert mode to exceed the Max
Discharge Current limit for inrush periods to startup loads such
as pumps/motors. When the timer expires, the Conext XW Pro
disables INV output.
Conext XW Pro Owner's Guide Configuration
62 This document is intended for use by qualified personnel 990-91227A-01