Conext XW PRO 6848 6,800W 48V Installation
Table Of Contents
- Safety Information
- Label Symbols
- Product Labels
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Monitoring Operation
- External Monitoring Control
- Configuration
- Troubleshooting
- Specifications
- Electrical Specifications
- Mechanical Specifications
- Regulatory Approvals
- Grid Support Utility Interactive Functions
- California Rule 21: Smart Inverter Grid-Support Utility Interactive Functions
- Hawaiian Electric Company (HECO) Rule No. 14: Smart Inverter Grid-Support Uti...
- IEEE 1547-2003 Standard for Interconnecting Distributed Resources with Electr...
- Puerto Rico Energy Power Authority (PREPA) Technical Requirements for Interco...
- Defaults
Figure 17 Equalize Charging Grid-tie Sell Mode
Time
Time
Absorption Voltage
Equalize Voltage
Max Absorb Time - Dflt 3 hrs
(adjustable 1 min - 8 hrs)
Boost Timer
1hr fixed
Absorption Exit Current
Threshold = 2% of
programmed AH capacity
Equalize mode
Custom Charge
Equalize Stage
Absorption Stage
Bulk Stage
Bulk Voltage=Boost Voltage
Battery
Current
Battery
Voltage
10% of programmed AH
capacity
Equalize Timer
1hr fixed
Configuration Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 71