Network Terminators
The Xanbus network must be properly terminated at each end to help ensure the
communication signal quality on the network.
Note: If the network is not properly terminated, signal quality is degraded and
performance on the network is reduced. Permanent configuration without terminators
is not supported.
The Conext XW Pro and other Xanbus-enabled devices ship with one network
terminator. Depending on your network layout, this terminator may need to be removed
from the Conext XW Pro Inverter/Charger and inserted into another device elsewhere in
the network.
Figure 59 Network terminator
Xanbus Clip-on Ferrite Bead
A clip-on ferrite bead is included to aid in suppressing high frequency electrical noise on
the Xanbus network. For optimal results, place the ferrite bead as close to the Conext
XW Pro ports as possible.