Conext XW PRO 6848 6,800W 48V Manual
Table Of Contents
- Safety Information
- Label Symbols
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Pre-Installation Planning
- Wiring
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW Pro with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW Pro units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW Pro Inverter/Charger without a PDP
- Communication
- Access Installation
- Specifications
- Wiring Diagrams
- Converting Split-phase to Single-phase
Depending on your installation, additional hardware may be required. The following items
are not included with the Conext XW Pro:
n Battery cables
n Grounding wire: #14 AWG to #2 AWG (1.63mm to 6.54mm)
n Lag bolts to secure the mounting plates
n Hacksaw for cutting busbars
n Screws for mounting the Conduit Box
n Additional wiring to connect the PDP to the inverter load sub-panel and utility grid
n Appropriate materials and hardware for additional wall-mount support
Location
The Conext XW Pro is certified for dry, indoor (heated or unheated) installations only.
Locate any electronic equipment susceptible to radio frequency and electromagnetic
interference as far away from the inverter as possible.
Fire safety
WARNING
IGNITION AND FIRE HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do not install this
product in locations that require ignition-protected equipment. This includes any confined
space containing lead acid batteries, or flammable chemicals such as, natural gas (NG),
liquid petroleum gas (LPG) or gasoline (Benzine/Petrol).
n Do not install in a confined space with machinery powered by flammable chemicals, or
storage tanks, fittings, or other connections between components of fuel or flammable
chemical systems.
n Do not install the inverter near readily flammable materials such as cloth, paper, straw,
or plastic sheeting. Keep flammable materials a minimum distance of 600 cm (24 in.)
from the top surface and 30 cm (12 in.) from either side surface and the front of the
Conext XW Pro Inverter/Charger.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Clearance Requirements
Provide at least 91 cm (36 in.) of clearance in front of the inverter, and a minimum of 15
cm (6 in.) of clearance at the top and bottom of the inverter for ventilation. Ensure the
vents remain unobstructed, and that the Conext XW Pro Power Distribution Panel door
has adequate room to fully open.
Pre-Installation Planning Conext XW Pro Installation Guide
990-91228A-01 This manual is intended for use by qualified personnel 26