Conext XW PRO 6848 6,800W 48V Manual
Table Of Contents
- Safety Information
- Label Symbols
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Pre-Installation Planning
- Wiring
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW Pro with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW Pro units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW Pro Inverter/Charger without a PDP
- Communication
- Access Installation
- Specifications
- Wiring Diagrams
- Converting Split-phase to Single-phase
Figure 13Mounting plate dimensions
16”
4 ½”
2”
6”
1 ¾”
17”
6
7
8
” 9
3
16
”
2 ¼”
¾”
Note: If the wall does not have 16-inch on-center studs, you will need to provide
adequate support for the Mounting Plates. For example, a sheet of fire-rated plywood
2
can be attached to the wall, and the Mounting Plates can then be attached to plywood.
Installing the Mounting Plate
To install the mounting plate:
1. Locate the wall studs.
2. If necessary, secure a ¾" fire-rated plywood
3
panel or other appropriate additional
support panel to the wall studs. The additional support panel must span at least three
wall studs.
Note: To secure the additional support panel to the wall, use hardware sized to
support a minimum of 500 lbs. (Hardware not included.)
3. Using a level, secure the first mounting bracket to the wall. Verify that the mounting
plate is centered on the wall studs, as shown in Figure 14. Use recommended
anchoring hardware to secure the plate, see Table 1.
2
Fire rated (treated fire resistant plywood can only be used in regions where natonal and local
building code allow the use of such materials. Use similar alternative building materials where
the building codes do not allow for fire rated wood products for electrical installations.
3
Fire rated (treated fire resistant plywood can only be used in regions where natonal and local
building code allow the use of such materials. Use similar alternative building materials where
the building codes do not allow for fire rated wood products for electrical installations.
Conext XW Pro Installation Guide Pre-Installation Planning
31 This manual is intended for use by qualified personnel 990-91228A-01