Conext XW PRO 6848 6,800W 48V Manual
Table Of Contents
- Safety Information
- Label Symbols
- Radio Frequency Interference Notices
- Audience
- About
- Product Safety Information
- Introduction
- Pre-Installation Planning
- Wiring
- Removing the AC Access Panel and PDP Internal Faceplates
- Communication Ports and BTS Port
- Wiring the Conext XW Pro with a PDP
- Basic Functional Test – Single Inverter
- Wiring Additional Conext XW Pro units with a PDP
- Basic Functional Test - Multiple Inverters
- Wiring the Conext XW Pro Inverter/Charger without a PDP
- Communication
- Access Installation
- Specifications
- Wiring Diagrams
- Converting Split-phase to Single-phase
AUX Port Terminal Assignments
Pin Reference Name Function
JU-1 AUX+12V
+12V User
Voltage Supply
+12VDC Voltage source: 250mA
maximum
JU-2 AUX-RPO
Remote Power
Off
Remote Power Off Logic Level: Active
Low. Activating this signal shuts down
system operation
JU-3 AUX-COM
Common Ground
Reference
Return Common Ground Reference
for 12V, Remote Power Off signals
JU-4 EXT_TS_OUT
External Transfer
switch: Output
signal
Open collector type drive circuit
(30V/0.5A max)
JU-5 EXT_TS_IN
External Transfer
switch: Input
signal
External Transfer switch: Low signal
range:(0-5V) High signal range:10-
28V with the consumption of
8mA@12V and 10mA@24V
Table 11User Connector Terminals and Functions
Conext XW Pro Installation Guide Wiring
49 This manual is intended for use by qualified personnel 990-91228A-01