a. the first Conext XW Pro Inverter/Charger (INV1) and
b. the battery bank
Note: Before connecting the DC cables from the PDP to the battery, perform the
procedures in "AC Wiring for a Dual-Inverter System" on page79.
2. Connect the positive battery cable for INV2 (included with the Connection Kit for
INV2 INV3 PDP) to the top terminal on the second DC disconnect/breaker, as shown
in Figure 43 .
3. Connect the negative battery cable for INV2 (included with the Connection Kit for
INV2 INV3 PDP) to the DC Negative Bus.
4. Connect the positive battery cable to the positive terminal on the second Conext XW
Pro (INV2) and the negative battery cable to the negative terminal on INV2.
Figure 43 DC Connections to Dual Inverter
Conext XW Pro Installation Guide Wiring
77 This manual is intended for use by qualified personnel 990-91228A-01