n Actual wiring requirements may vary.
n Cable routing may vary. See "Knockout Selection" on page28 and "Communications
Network Preparation" on page36.
n See "Torque Values" on page40 for torque values. For torque connections to the
battery terminals, see the battery manufacturer's recommendations.
Installing Bypass Interlock Plate
To install the custom designed bypass interlock plate:
1. Replace the upper and lower faceplates on the PDP.
2. Verify that the breakers are in the down position and place the bypass interlock plate
over the breakers, as shown in Figure 46 , and secure it in place with the hardware
provided.
3. To set it in Normal position, slide the bypass plate to the right, as shown in Figure 46 .
Figure 46 Installing the Custom Designed Bypass Interlock Plate
Installing a Triple Inverter/Charger System
NOTICE
EQUIPMENT DAMAGE
n The Automatic Transfer Relays are rated at 60 A.
n Loads connected at AC OUT must not exceed the inverter's overload ratings or the 60 A
limit, whichever is lower. Unless an external contactor or external transfer switch is
used, the 60 A limit also applies to loads connected to the AC OUT bus of multiple
inverters connected in parallel.
Failure to follow these instructions can result in equipment damage.
Conext XW Pro Installation Guide Wiring
81 This manual is intended for use by qualified personnel 990-91228A-01