Grounding the DC System
To connect the Conext XW Pro to the DC grounding system, use the ground lug at the
bottom of the Conext XW Pro chassis (see Figure 2 on page 18). The terminal accepts
wires from #14 AWG (1.63 mm) to #2AWG (6.54 mm).
System grounding for the DC system, which typically involves bonding (connecting) the
battery negative circuit to ground, is dependent on the system configuration.
Note: If a grounded DC system is required, ensure that the system bonding is done in
one location only, and that all conductors and connections comply with all applicable
NEC and local installation codes.
Figure 51 Grounding the DC System (No PDP)
Wiring Conext XW Pro Installation Guide
990-91228A-01 This manual is intended for use by qualified personnel 92