Easy UPS
SRV Series Extended Runtime
1000VA,
2
000VA, 3000VA
UPS Settings
Configure UPS settings using the display interface. See “Configure UPS
parameters” section to edit the
parameters.
Function
Factory Default
User Selectable Options
Description
Output voltage
230 Vac
220, 230, 240 Vac
Allows the user to select output
voltage while the UPS is operating
online.
Audible alarm
Enable
Enable, disable
UPS will mute audible alarms when
setting to
disable
or when the display
panel MUTE
button is pressed.
Green mode/
high efficiency
mode
Disabled
Enable/Disable
When this mode is enabled, connected
equipment receives utility input power
through the bypass relay as long as
input voltage is within the range of ±5%
of configured output voltage and ± 3 Hz
of configured output frequency. Inverter
is turned off during this mode.
If utility power input goes out of
range, inverter is turned on. The load
is transferred to online mode or battery
mode. The power to the connected
equipment may be interrupted up to 10
milliseconds.
Minimum
battery capacity
to restart setting
0%
0%, 15%,50%,90%,
UPS output will not be turned on until
the battery is charged to a level such
that it can provide the runtime
configured by this setting. If configured
to 0%, UPS output is turned on
immediately after utility power returns.
Low battery state
indication setting
2 min
2 min, 5 min, 7min,
10min,
The UPS will emit audible alarm when
the actual run time reaches the limit set
by the end user. The audible alarm will
emit only when the UPS is working in
battery mode.