Problem and/or Possible Cause
Solution
UPS is not turning off
POWER OFF button not pressed properly
Press and hold the button until the beep is heard
to power off the UPS.
Utility input power is available.
UPS logic power can not be turned off if utility input power
is available. To turn off the UPS, turn off utility input
power and press button. Release when a beep is
heard.
UPS is in Bypass mode and the LED is not illuminated red.
UPS is in green mode.
Disable green mode if not desired.
UPS is configured to stay in the bypass
mode.
Change the configuration to exit bypass mode.
UPS is in bypass mode even after over
temperature alarm is cleared.
Reduce the connected load to <90% to bring the UPS to
online mode.
The UPS has experienced an overload
condition and transferred to bypass.
Connected equipment exceeds the “maximum load” as
defined in specifications on the APC
by Schneider
Electric
Website, www.apc.com.
The alarms remain on until the overload condition is
corrected. Disconnect nonessential equipment from the
UPS to eliminate the overload condition.
The UPS continues to supply power as long as it is in
bypass mode and the circuit breaker does not trip. The
UPS will not provide battery power in the event of a utility
voltage interruption.
UPS detected an error and transferred to
bypass.
See “Alarms and Notifications” on page 11 in this manual.