User Manual
4
Easy UPS
SRV Series
Extended Runtime 1000VA,
2
000VA, 3000VA
Specifications
Environment Specifications
NOTICE
RISK OF EQUIPMENT DAMAGE
•
UPS must be used indoors only.
•
The installation location should be sturdy to withstand the weight of the UPS.
•
Do not operate UPS where there is excessive dust or where the temperature or humidity are outside specified limits.
Failure to follow these instructions can result in equipment damage.
Temperature
Operating
0° to 40°C at rated load.
40° to 50°C linearly derated to 80% of
maximum load capacity.
This unit is intended for indoor use
only. Select a location sturdy enough
to handle the weight.
Do not operate UPS where there is
excessive dust or where the
temperature or humidity are outside
specified limits.
Storage
-20° to 50°C
Elevation
Operating
0 - 1,000 m: normal operation
1,000 - 3,000 m: The load reduces @
1% at an increased height of every
100 m
> 3,000 m: UPS will not work
Storage
0 - 15,000 m
Humidity
0 to 95% relative humidity, non-
condensing
IP Rating
IP 20
Physical Specifications
UPS model
SRV Extended Runtime
1000VA
SRV Extended
Runtime 2000VA
SRV Extended Runtime
3000VA
Dimensions with package
Width x Height x Depth
235 mm (9.25in) x 330
mm (12.99in) x 365 mm
(14.37 in)
235 mm (9.25in) x 330
mm (12.99in) x 477 mm
(18.78 in)
235 mm (9.25in) x 330
mm (12.99in) x 477 mm
(18.78 in)
Dimensions without
package
Width x Height x Depth
145 mm (5.7 in) x 223
mm (8.78 in) x 288 mm
(11.34 in)
145 mm (5.7 in) x
238mm (9.37in) x 400
mm (15.75 in)
145 mm (5.7 in) x
238mm (9.37in) x 400
mm (15.75 in)
Weight with package
5.9kg
9.1kg
9.6kg
Weight without package
4.4kg
7.4kg
7.9kg
Lifting guidelines
< 18 kg (< 40 lb)
< 18 kg (< 40 lb)