User Manual
5
Easy UPS
SRV Series Extended Runtime
1000VA,
2
000VA, 3000VA
Input/Output Specifications
UPS Model
SRV Extended
Runtime 1000VA
SRV Extended
Runtime 2000VA
SRV Extended
Runtime 3000VA
Input
Voltage
230 Vac Nominal
Frequency
40 – 70 Hz
Input Voltage Range
(100% load)
160 Vac – 280 Vac
Input Voltage Range (50%
load)
110 Vac – 285Vac
Input Power Factor (100%
resistive load)
≥ 0.95
Input Protection
Input circuit breaker
Output
UPS Capacity
1000 VA / 800 W
2000 VA / 1600 W
3000 VA / 2400 W
Nominal Output Voltage
230 Vac
Other Programmable
Voltage
220 Vac, 240 Vac
Efficiency at rated load
88% max.
Output Voltage Regulation
± 1% static
Output Voltage Distortion
•
3% max. for full linear load,
•
6% max. for full RCD load (100% VA, 0.8 PF)
•
15% for the last 60 seconds of the backup time (with full
load only for the internal battery)
Frequency – On Battery
50 Hz ± 0.5% or 60 Hz ± 0.5%
Frequency – AC Mode
50 Hz ± 3 Hz or 60 Hz ± 3 Hz
Crest Factor
3:1
Waveform
Sinewave
Output Connection
Please refer to rear panel features
Bypass
Internal bypass
Battery
UPS Model
SRV Extended
Runtime 1000VA
SRV Extended
Runtime 2000VA
SRV Extended
Runtime 3000VA
Configuration
External battery
Type
Sealed maintenance free (SMF) 12 V, 9 Ah
Charging Current
4 A
Battery Bank Voltage
36 V
72 V
72 V
Front Panel Display
UPS Power On/Off button
Status LED
LCD Display
Mute/Esc button
Enter button
Up / Down button
Alarm LED