Installation Guide
975-0691-01-01 Revision B 3-29
Main Battery Settings
10-2 1
F1.6 Auto-sync sensitivity. Changes sensitivity of the auto-sync function. If
it takes too long to activate the synchronization function, lower this
value. If it synchronizes too early, increase this value for a later
synchronization.
Default Range Step size
50-10 1
F2.0 Battery capacity. Your Main battery’s capacity in Amp hours (Ah).
Default Range Step size
200 20-9990 Variable
F2.1 Nominal discharge rate (C-rating). Set in conjunction with battery
capacity, F2.0.
Default Range Step size
20h 1-20h 1
F2.2 Nominal temperature. The temperature at which the battery
manufacturer rates your battery’s capacity. Set in conjunction with
battery capacity, F2.0.
Default Range Step size
+20°C 0 – 40°C 1°C
F2.3 Temperature coefficient. This is the percentage that your battery’s
capacity changes with temperature. The unit of this value is percent
capacity per degree Celsius. The setting “OFF” disables
temperature compensation.
Default Range Step size
0.50% capacity 0.01 – 1.00% capacity 0.01% capacity
F2.4 Peukert’s Exponent. Represents the effect of reducing battery
capacity at higher discharge rates. Properly setting Peukert's
exponent ensures a more accurate display of time remaining and
percent remaining. Note: Consult your battery manufacturer to
understand the value to use based on your model. Refer to
“Peukert’s Exponent for Battery Rating” on page 4–45 for further
details.
Default Range Step size
1.25 1-1.50 0.01
F2.5 Self-discharge rate. Rate at which the battery loses capacity by itself
when not used.
Default Range Step size
OFF 0.1-25% / Month 0.1
F2.6 Charge Efficiency Factor. Ratio between the energy removed from a
battery during discharge and the energy used during charging to
restore the original capacity. See “How the Charge Efficiency Factor
is used” on page 4–44 for more information.
Default Range Step size
AUTOMATIC 50-100%, AUTOMATIC N/A