Installation Guide

975-0691-01-01 Revision B 4-43
Meters
When not being actively configured, the Battery Monitor is operating in display
mode. By default, it displays the main battery voltage readout. To display one of
the other meters:
Press the OK button repeatedly until the desired indicator illuminates.
The LCD display will indicate the values for the currently selected function.
All readout selections can be navigated by using the < and > keys.
The standard readout selection sequence is as follows:
V (battery voltage) > A (charge/discharge current) > Ah (Amount of consumed
Amp-hours) > % (State-of-charge (SOC) > h (Time remaining until a battery
recharge is necessary) > °C (Battery temperature, or temperature setting if BTS
is installed) > V (Mid Point Voltage, if configured).
Available Meters
V (Volts) When this indicator is displayed, the LCD display shows the voltage currently
present at the battery. The range is 0 to 70 Volts. The accuracy is ±0.3%.
A (Amps) When this indicator is displayed, the LCD display shows the currently occurring
charge or load current in amps. The range is from ±0.1 to ±9999 amps with a
refresh rate of one second. The accuracy is ±0.4%.
Ah (Amp-hours) When this indicator is displayed, the LCD display shows the total amp-hours
used since the last time the amp-hour meter was reset. The range is from ±0.00
to ±9990 amp-hours. When the decimal point flashes, it means that more than
10,000 amp-hours have accumulated. In this case, multiply the reading by 1000
(i.e., 111 = 111,000). This meter automatically resets to zero approximately one
minute after the Full LCD stops flashing.
% (State-of-
charge)
When this indicator is displayed, the LCD display shows the battery’s State-of-
charge based upon the amp-hour reading divided by the amp-hour capacity of
the batteries (or battery bank). The values displayed are:
Lo (when battery is below 27.5%)
30 to 90% numerical value (in 5% increments)
Full (when the battery’s State-of-charge is over 92.5% capacity)
h (Time Remaining) Time remaining until recharge. Limit represented in HH:mm remaining time.
This readout displays “-----” when charging.
°C (Battery Temp) Battery temperature. Indicates the battery temperature if the Battery Temperature
Sensor (BTS) is installed. Otherwise, this will display the temperature as set in
Function F1.4.
V (AUX Volts) Displays the mid-point voltages Va1 and Va2 when mid-point voltage sensing is
used. When selected, this setting will alternate between displaying Va1 and Va2.
See “Mid-point sensing configurations” on page 3–35 for more information.