Context XW Connection Kit for Second Inverter Specifications

Compatible AC breakers for XW
Power Distribution Panel
XW Series Power Distribution | 5
Application Compatible Breakers
UL Standards
120/240 VAC
60 A, 120/240 VAC Breaker Kit (865-1215-01); or
Customize with Square D type QOU DIN-rail mount breakers
120/208 VAC
60 A, Three-Phase Breaker Kit (865-1315-01); or
Customize with Square D type QOU DIN-rail mount breakers
IEC Standards
230 VAC Schneider Electric Acti9 and Multi9 DIN-rail mount breakers
60 A, 120/240 VAC Breaker Kit
XW Conduit Box
Part number 865-1215-01
The 60 A, 120/240 VAC Breaker Kit is used for AC distribution for a second or third XW inverter
connection to the Power Distribution Panel. If the Power Distribution Panel was ordered with
AC breakers, a single breaker kit can be used for connecting two or three inverters. With two
inverters, the three additional breakers are used for AC in (grid), bypass, and AC Out (load).
With three inverters the breakers in the PDP are used for AC in (grid) and AC Out (load), and
bypass functionality would be installed externally (not included). Includes:
Three 60A, 120/240 Vac, two-pole, Square D, type QOU, DIN-rail mountable AC breakers
Four Jumpers with four tabs each
Bypass interlock plate for dual inverter systems
60 A, Three-Phase Breaker Kit
Three-Phase Breaker Kit for XW PDP
Part number 865-1315-01
The 60 A, Three-Phase Breaker Kit is used to connect three XW+ inverters in a 120/208V three
phase configuration in the Power Distribution Panel. The three, 60A three-pole breakers are
used for connecting AC In (grid), bypass, and AC Out (load). Includes:
Three 60A, 120/208 Vac, three-pole, Square D QOU360, DIN-rail mountable AC breakers
Power distribution jumpers
Bypass interlock for three-phase systems using three XW inverters