Quick Start Guide
O
Technical Specifications
Conext Battery Monitor
●
18..66 VDC
80 mA @ VIN=48 VDC, 150 mA @ VIN=24 VDC
<4W
0..70VDC
2..70VDC
-9999..+9999A
20..9990Ah
-20..+50˚C
Parameter
Electrical Specifications
Supply Voltage
Supply Current*
Power Consumption
Input Voltage Range (main batt.)
Input Voltage Range (aux. batt.)
Input Current Range
Battery Capacity Range
Operating Temperature Range
* (Backlight off, logging disabled)
0..70 (+0.01 V)
0..200A / 200..9999A (+0.1A / +1A)
0..200AH / 200..9990Ah (+0.1Ah / +1Ah)
0..100% (+0.1%)
0..24hrs / 24..240hrs (+ 1 minute / + 1hr)
-20..+50˚C (+ 0.5˚C)
Resolution
Voltage
Current
Amp-Hours
State-of-charge
Time Remaining
Temperature ()
Accuracy
Voltage Measurement
Current Measurement
Connections
Battery Voltage, Shunt/Temp Sensor
USB 2.0 – Device
+/- 0.3%
+/- 0.4%
RJ45 / RJ12 ( cables included)
Connector: USB min-B, Protocols: MSD (data
extraction)
Features
Network
USB 2.0
ModBus
Data Logging
Display
Front-panel interface
Battery string-imbalance detection
Temperature Sensor (included)
Warranty
Protocol: Xanbus / Connectors: RJ45
Protocol: MSD (data extraction) Connector: USB
min-B
Isolated RS-485, 2-wire serial
10 data points every 10 minutes for 10 years
Backlit LCD
3 menu buttons, 1 power button
Two-point sensing
762cm
2 to 5 years (depending on country)
Mechanical Specifications
Dimensions
Weight
IP Rating/Mounting location
Storage Temperature Range
Part number
Battery Interface Kit with Shunt
(Included)
Connection to Battery
Connection to Battery Monitor
Shunt
Shunt Dimensions
Shunt Weight
Regulatory Standards
Markings
EMC
8.5 x 8.5 x 9.0cm
0.2kg
IP 20, NEMA 1, Indoor Only
-30..+60˚C
865-1080-01
300cm cable with ring-terminals
500cm CAT5 cable RJ45
500A / 50mv
8.7 x 4.5 x 3.5 cm
0.15 kg
●
CE
Directive 2004/108/EC, IEC/EN61000-6-3,
IEC/EN61000-6-1, FCC Part 15 Class B,
Industry Canada ICES-003 Class B
M
Configuration using the Conext System Control Panel
• Conext XW+ 5548 NA / Conext XW+ 6848 NA
• Conext XW +7048 E / Conext XW + 8548 E
• Conext SW 2524 230 / Conext SW 4024 230
• Conext SW 2524 120 / Conext SW 4024 230
• Conext MPPT 60 150
• Conext MPPT 80 600
• Conext SCP
• Conext AGS
• Conext ComBox
N
Compatible Products by Schneider Electric
The Conext System Control Panel (SCP) provides remote configuration and monitoring
capability for the Battery Monitor and all other Xanbus-enabled devices in the network.
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION;
(
B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH
MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE
ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM.
4
www.SEsolar.com
Conext™ Battery Monitor
865-1080-01
MAIN
MAIN
MAIN
F1
System Properties
F3
Battery Monitor Settings
MAIN
F2
Main Battery Properties
Default
52.8V
50%
200Ah
20h
20°C
500A
50mV
30s
°C °C °F
OFF ON
Min
16V
0%
20Ah
1h
0°C
10A
50mV
OFF/5s
Max
64V
99%
9990Ah
20h
40°C
9000A
60mV
300s/ON
Description
Battery charger’s float voltage, which is the
last stage of the charging process.
Reference point at which the battery needs to
be recharged. When SOC< this value the
Charge battery indicator starts flashing, the time
remaining shows 0:00 & SOC bar is empty.
Battery’s capacity in Amp-hours (Ah)
The discharge rate (in hours) at which the
battery manufacturer rates your battery’s
capacity.
The temperature at which the battery
manufacturer rates the battery’s capacity.
Amp rating of connected shunt
Battery monitor supports only 50mV and
60mV shunts
Period of backlight activation in seconds after
key-press
Select display between °C/°F
When set to “ON”, all Push buttons on
physical unit is locked
Function
F1.0
Float voltage
F1.3
Discharge floor
F2.0
Battery Capacity
F2.1
Nominal Discharge Rate
F2.2
Nominal Temperature
F3.1
Shunt Amp Rating
F3.2
Shunt milliVolt Rating
F3.3
Backlight mode
F3.4
Temperature unit
F3.5
Setup lock
I
J
Default
200
19200
Even
1
LSB First
Min
1
9600
Odd
1
LSB
Max
255
115200
None
2
MSB
Modbus Setting
RS485 Address
RS485 Baud Rate
RS485 Parity
RS485 Stop Bits
Modbus Byte Order
Modbus settings on your Battery Monitor are not configurable via the Function menu. These settings can be
configured with a Conext System Control Panel, ComBox or Conext Configuration Tool:
L
Default
1
0.50%
cap/°C
1.25
3.0%
/month
Au
Min
0
0.01
1.00
OFF /
50%
Max
2
1.00%cap/
°C
1.50
25.0%
/month
Au
Description
Represents effect of reducing battery
capacity at higher discharge rates.
Percentage that battery’s capacity changes
with temperature.
Represents effect of reducing battery
capacity at higher discharge rates.
Rate at which the battery loses capacity by
itself, when it is not used.
Ratio between the energy removed from a
battery during discharge & the energy used
during charging to restore original capacity.
Function
F1.5
Time remaining averaging filter
F2.3
Temperature coefficient
F2.4
Peukert's exponent
F2.5
Self-discharge rate
F2.6
Charge Efficiency Factor
K
Copyright © 2014 Schneider Electric. All Rights Reserved.
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Function Menu Tree
Essential Settings
Modbus Settings
Advanced Settings
Conext SCP
Battery Monitor menu
[Faster]
Conext BM 00 : Adv
Peukert Expo [1.25V]
Charge Eff [Auto]
Temp Coeff
Sync Sensitivity
[0.5%]
[3]
Time Rem Filter
Multi Unit Config
Restore Defaults
Conext BM 00 : Basic
Capacity [450Ah]
Discharge Rate [20h]
Shunt Amps [500A]
Shunt mV [50mV]
Self Disch [3.0%]
Discharge Floor [50%]
Float Volt [52.8V]
Float Amps [2%]
Temp Unit [Celsius]
Nominal Temp [25øC]
Back Light Timer [30]
Auto Sync Time [240]
Advanced Settings
Basic Settings
Mode [Standby]
Battery Temp
28øC
Time Remaining
03:56 h:m
AH Removed
-150Ah
State of Charge
75%
Battery
31.7A
57.4V
RS485 Settings
Synchronize Now (control button)
Mid Points 23.8V23.7V
Conext BM 00: RS485 Sett
Address [001]
Baud Rate [119200]
Parity [Even]
Stop Bits [One]
Byte Order [LSB]
Conext BM 00 : Multi
Dev Name
Dev Number
DC Conn
Conext BM 00 : Meters
[BM1]
[00]
[HouseBatt1]