Conext Configuration Tool Manual

Device Configuration
3–30 975-0720-01-01
This manual is for use by qualified personnel only
Trigger Configuration
Trigger Configuration contains the settings for automatically starting and
stopping the generator. This menu allows the adjustment of the default settings
for battery voltage, thermostat ON/OFF signals, inverter load, and battery
charging stage.
Note: To automatically start and stop the generator using these triggers, the
trigger must both be set and enabled. Some triggers need to be enabled only.
Figure 3-27 AGS Trigger Configuration
Table 3-12 AGS Trigger Settings
Setting Description
Low Battery
Voltage
Start (30 sec)
Enables the AGS to start the generator whenever the battery voltage reaches or
drops below a pre-set voltage for longer than 30 seconds.
Low Battery
Voltage
Start (15 min)
Enables the AGS to start the generator whenever the battery voltage reaches or
drops below a pre-set voltage for longer than 15 minutes.
Low Battery
Voltage
Start (2 hr)
Enables the AGS to start the generator whenever the battery voltage reaches or
drops below a pre-set voltage for longer than 2 hours.