Conext Configuration Tool Manual

Configuring the Conext Automatic Generator Start
975-0720-01-01 3–31
This manual is for use by qualified personnel only
Low Battery
Voltage
Start (24 hr)
Enables the AGS to start the generator whenever the battery voltage reaches or
drops below a pre-set voltage for longer than 24 hours.
Charger Float
State Stop
When selected, enables the AGS to stop the generator when the inverter/charger has
recharged the batteries to the Float stage.
Charger
Absorption
State Stop
When selected, enables the AGS to stop the generator when the inverter/charger has
recharged the batteries to the Absorption stage.
Above Battery
Voltage Stop
Enables the AGS to stop the generator whenever the battery voltage reaches a pre-
set DC voltage. Whenever the generator starts automatically based on the Starting
Battery Voltage, it will shut off once the Stopping Battery Voltage has been reached.
AC Load Start/
Stop
Enables or disables the Start Load and Stop Load functionality of the AGS. This
function enables the generator to start and stop based on the current being drawn on
the inverter by the loads.
Above AC Load
Start
Enables the generator to start at a specified AC load (current draw) on the inverter.
This current draw must be present for 5 minutes before the generator will start. The
generator will assist the inverter with powering the AC load.
Below AC Load
Stop
Enables the AGS to stop the generator when the AC load falls below a specific level
for 1 minute.
Thermostat 1
Start/Stop
When selected, enables the generator to start in response to a signal from a
thermostat. With Temp1 enabled, the AGS will start the generator to help power the
item controlled by that thermostat.
Thermostat 2
Start/Stop
When selected, enables the generator to start in response to a signal from a second
thermostat.
Table 3-12 AGS Trigger Settings
Setting Description