Conext Configuration Tool Manual

Using the Configuration Wizard
975-0720-01-01 2–11
This manual is for use by qualified personnel only
6. Set the XW Inverter/Charger Custom Battery Settings. (This screen is active if
you selected Custom as the battery type in the previous screen. Otherwise
the screen is unavailable.)
The Custom Settings screen allows you to adjust charging and equalization
voltage for batteries with specifications that fall outside the default settings
for the battery types the Conext XW Inverter/Charger offers.
Battery Capacity Selects the system battery capacity in amp-hours.
Charger Enabled Enables or disables the charger.
Maximum Charge
Rate
Sets the percentage of the maximum DC output current that is available to the
charger. Refer to the Owner’s Guide for your inverter to determine the maximum
DC output current for different models.
Charge Cycle Sets the charging method: 3Stage (Bulk, Absorption, Float) and 2StageNoFloat
(Bulk, Absorption, NoFloat).
Recharge Volts Sets the battery voltage level at which a new charge cycle begins.
Inverter Enabled Enables of disables the inverter.
AC Input Priority Sets the priority for the AC source (AC1 or AC2) for qualification and transfer. For
example, this setting allows the inverter/charger to use a renewable energy
source (such as an AC hydro generator) connected to AC2 on a first-priority
basis and use utility power only when renewable energy is insufficient or
unavailable to power loads.
AC1 Breaker Rating Sets the AC1 (Grid) breaker size, based on the size of the breaker installed on
AC1.
AC2 Breaker Rating Sets the AC2 (Gen) breaker size, based on the size of the installed AC breaker.
Low Battery Cutout Controls when the inverter turns off due to a low battery voltage condition.
Table 2-1 XW Inverter/Charger Settings
Setting Description