Conext Configuration Tool Manual

System Configuration
2–12 975-0720-01-01
This manual is for use by qualified personnel only
You can also adjust the temperature compensation constant for the Battery
Temperature Sensor on the Custom Battery menu.
WARNING
BATTERY TYPE AND SETUP HAZARDS
Incorrect battery configurations or settings for battery types can lead to
dangerously high battery temperature, fire and explosion. To avoid damaging
your batteries during charging or equalization, and to minimize the risk of fire
or explosion consult battery manufacturer's documentation before setting
battery parameters and follow the battery manufacturer's recommended
settings.
• Always use and connect the Battery Temperature Sensor (BTS).
• Always verify that the configured battery type matches the battery type
being used.
• Custom battery settings should be configured by qualified personnel only.
• When using Lithium-Ion batteries, ensure that the battery pack being used
includes a Battery Management System (BMS) with safety controls.
Failure to follow these instructions can result in death or serious injury.
Figure 2-13 XW Inverter/Charger Custom Battery Settings
Table 2-2 XW Inverter/Charger Custom Battery Settings
Setting Description
Battery Type The system battery chemistry and type. In the Custom menu, Custom is pre-selected
and cannot be changed
Charge Cycle Sets the charging method: 3Stage (Bulk, Absorption, Float) and 2StageNoFloat (Bulk,
Absorption, NoFloat).
Equalization
Support
Enables or disables the ability to enter an equalization cycle. Refer to the battery
manufacturer’s specifications to determine whether equalization is recommended.