Conext Configuration Tool Manual

Using the Configuration Wizard
975-0720-01-01 2–19
This manual is for use by qualified personnel only
5. Set the XW Inverter/Charger Inverter Settings.
Figure 2-20 XW Inverter/Charger Inverter Settings
Table 2-5 Conext XW+ Inverter/Charger Inverter Settings
Setting Description
Inverter Enabled Enables the inverter when selected.
Low Battery Cut
Out
Controls when the inverter turns off due to a low battery voltage condition. The
inverter will turn off only after this level has been reached for the period of time set by
the LCBO Delay. This setting is not temperature compensated.
Low Battery Cut
Out Delay
Controls how long the inverter is allowed to operate at or below the Low Battery Cut
Out level before turning off due to a low battery voltage condition. The inverter will
turn off only after the Low Batt Cut Out level has been reached for this uninterrupted
period of time.
High Battery Cut
Out
High Batt Cut Out sets the maximum battery voltage at which the inverter will
operate. If the battery voltage exceeds this limit for more than 1 minute, the inverter
displays a fault message (F49) and shuts down. The inverter will not support AC
loads when in this condition. If a qualified AC source is present, the unit passes AC
through to the loads.
Search
Threshold
Search Threshold sets the inverter’s search sensitivity when Search mode is
enabled. When a load larger than this setting is present, the inverter turns on.
Search Delay Search Delay sets the time between search pulses. When searching for loads, the
inverter/charger sends out search pulses to determine if a load is present. If the
inverter/charger finds a load above the Search Watts setting, the inverter comes on.