Conext Configuration Tool Manual

Using the Configuration Wizard
975-0720-01-01 2–21
This manual is for use by qualified personnel only
7. Set the Conext XW+ Inverter/Charger Custom Battery Settings. (This screen
is displayed if you selected Custom as the battery type in the previous
screen. Otherwise, the screen is unavailable.
AC1 Breaker
Rating
Sets the AC1 (Grid) breaker size, based on the size of the breaker installed on AC1.
The installed breaker size must not exceed the capacity of the upstream distribution
panel. The charger limits the maximum input current to this setting by derating its
charging current.
AC2 Breaker
Rating
Sets the AC2 (Gen) breaker size, based on the size of the breaker installed on AC2.
The installed breaker size must not exceed the capacity of the upstream distribution
panel. The charger limits the maximum input current to this setting by derating its
charging current.
Low Battery
Cut Out
Controls when the inverter turns off due to a low battery voltage condition. This setting
is not temperature compensated.
Table 2-6 XW Inverter/Charger Settings
Setting Description
Figure 2-22 XW Inverter/Charger Custom Battery Settings
Table 2-7 XW Inverter/Charger Custom Battery Settings
Setting Description
Battery Type The system battery chemistry and type. In the Custom menu, Custom is pre-selected
and cannot be changed
Charge Cycle Sets the charging method: 3Stage (Bulk, Absorption, Float) and 2StageNoFloat (Bulk,
Absorption, NoFloat), and External BMS.
Equalization
Support
Enables or disables the ability to enter an equalization cycle. Refer to the battery
manufacturer’s specifications to determine whether equalization is recommended.
Equalization
Voltage
Selects the equalization voltage. Consult your battery manufacturer for equalization
voltage setting.
Bulk Voltage Sets the bulk voltage for a custom battery type.
Absorb Voltage Sets the absorption voltage for a custom battery type.