Conext Configuration Tool Manual

Using the Configuration Wizard
975-0720-01-01 2–25
This manual is for use by qualified personnel only
10. Set the XW Solar Charge Controller Charger settings.
Load Shave
Amps
Sets the maximum amount of current that can be drawn from the AC1 (grid) input by the
loads and battery charger combined. This setting determines the amperage level at which
the inverter starts drawing power from the batteries to add to the utility power to meet the
demand of the loads.
Load Shave
Start
Sets the time of day that the Load Shave feature operates. This feature is suited for regions
where local utilities impose peak usage surcharges. The inverter provides load shaving
power as long as battery voltage is above the Low Batt Cut Out setting.
Load Shave
Stop
Sets the time of day that the Load Shave feature stops operating. If Load Shave is enabled
and Load Shave Start and Load Shave Stop are set to the same time, the inverter load
shaves continuously.
Sell Start Sets the time of day that the grid sell feature begins operating. Grid support must also be
enabled on the inverter for this feature to function.
Sell Stop Sets the time of day that the grid sell feature stops operating. Grid support must also be
enabled on the inverter for this feature to function.
Table 2-8 XW Inverter/Charger Grid Support Settings
Setting Description
Figure 2-26 Setting the XW Solar Charge Controller Charger Settings
Table 2-9 XW Solar Charge Controller Charger Settings
Setting Description
Battery Type Selects the system battery chemistry and type: Flooded (default), AGM, Gel, and
Custom.
If you select Custom, a screen for configuring voltage settings for each charging
stage is displayed after you click Next.
Battery Capacity Selects the system battery capacity in amp-hours.
Maximum
Charge Rate
Sets the percentage of the maximum DC output current that is available to the
charger. The maximum DC output current for the Charge Controller is 60 ADC.