Conext Configuration Tool Manual

System Configuration
2–30 975-0720-01-01
This manual is for use by qualified personnel only
5. A Battery Cluster Warning will appear advising that the battery changes will
apply across all clusters in the system. After taking note to adjust settings as
necessary, click next.
6. Set the XW Inverter/Charger Inverter Settings as outlined in step 5 of the
“Detailed Configuration Method”.
7. Set the XW + Charger Settings. Note that if Custom is selected as Battery
Type, the next screen will allow you to configure custom settings.
AC Coupling This function is enabled by default and should remain enabled except in cases
where the DC voltage level is allowed to have large variations and the AC line
frequency needs to remain constant.
Battery Energy
Balancing
This feature is intended for use with inverters drawing power from a single battery
bank. The Battery Balance function should be enabled when Conext XW+ units
are used in multi-cluster systems with multiple battery banks. When enabled, this
feature helps balance the power draw across multiple battery banks.
Table 2-12 Common Connection Association Settings
Setting Description
Figure 2-33 Setting the XW+ Charger Settings
Setting Description
Battery Type Selects the system battery chemistry and type: Flooded (default), AGM, Gel, Custom
and Lithium Ion.
If you select Custom, a screen for configuring voltage settings for each charging
stage is displayed after you click Next.
Battery
Capacity
Selects the system battery capacity in amp-hours.
Charger
Enabled
Enables or disables the charger.
Maximum
Charge Rate
Sets the percentage of the maximum DC output current that is available to the
charger. Refer to the Owner’s Guide for your inverter to determine the maximum DC
output current for different models.