Conext Configuration Tool Manual

Using the Configuration Wizard
975-0720-01-01 2–31
This manual is for use by qualified personnel only
8. If Custom was selected as Battery Type, set the Conext XW Inverter/Charger
Custom Battery Settings as detailed in Step 6 of the “Quick Configuration
Method”.
9. If Lithium Ion was selected as Battery Type, set the Conext XW Inverter/
Charger Lithium Ion Battery Settings.
Charge Cycle Sets the charging method: 3Stage (Bulk, Absorption, Float) and 2StageNoFloat (Bulk,
Absorption, NoFloat), and External BMS.
Recharge Volts Sets the battery voltage level at which a new charge cycle begins.
Absorption
Time
Sets the time spent in the Absorption stage, before transitioning to Float (3-Stage
charging) or NoFloat (2-Stage charging).
Default Battery
Temperature
Selects the battery temperature charging compensation if a battery temperature
sensor is not installed. In the absence of a battery temperature sensor, the charger
uses one of three settings: “Cool” (5 °C), “Warm” (25 °C), or “Hot” (40 °C).
Charger Block
Start
Sets the time to halt charging on AC1 (Grid). The AC2 (Gen) port is unaffected by the
Charger Block settings. The Charger Block Start and Stop settings allow you to select
when the charger stops charging on AC1.
Charger Block
Stop
Sets the time that charging on AC1 can resume. At the Charger Block Stop time,
charging on AC1 is enabled again.
Setting Description
WARNING
BATTERY TYPE AND SETUP HAZARDS
Incorrect battery configurations or settings for battery types can lead to
dangerously high battery temperature, fire and explosion. To avoid damaging
your batteries during charging or equalization, and to minimize the risk of fire
or explosion consult battery manufacturer's documentation before setting
battery parameters and follow the battery manufacturer's recommended
settings.
• Always use and connect the Battery Temperature Sensor (BTS).
• Always verify that the configured battery type matches the battery type
being used.
• Custom battery settings should be configured by qualified personnel only.
• When using Lithium-Ion batteries, ensure that the battery pack being used
includes a Battery Management System (BMS) with safety controls.
Failure to follow these instructions can result in death or serious injury.