Conext Configuration Tool Manual

System Configuration
2–32 975-0720-01-01
This manual is for use by qualified personnel only
10. Set the Conext XW+ AC Settings as outlined in Step 8 of the “Detailed
Configuration Method”.
11. Set the Solar Charge Controller Charger Settings as outlined in Step 10 of the
“Detailed Configuration Method”.
12. Set the Solar Charge Controller Input Settings as outlined in Step 12 of the
“Detailed Configuration Method”.
13. Save the System Configuration. See “Save the System Configuration.” on
page 2–16 for details.
Restoring a Configuration
By selecting Save Configuration from the Configure menu, you can choose a
previously saved or downloaded system configuration file that contains settings
for all devices.
Figure 2-34 Setting the Lithium Ion Battery Settings
Setting Description
Battery Type Pre-set to Lithium Ion as selected in the previous step.
Charge Cycle Sets the charging method: 3Stage (Bulk, Absorption, Float), 2StageNoFloat (Bulk,
Absorption, NoFloat), and External BMS.
Maximum
Discharge
Current
Specifies a percentage of battery current within which the contactor will open in case
of an overload.
Maximum
Discharge
Time
Specifies the interval in seconds between each verification of the Maximum Discharge
Current.