Table 3-1 Inverter Settings menu
Item Description
Inverter Enable Enables the inverter when selected.
Low Battery Cut
Out
Controls when the inverter turns off due to a low battery voltage condition. The
inverter will turn off only after this level has been reached for the period of time set by
the LCBO Delay. This setting is not temperature compensated.
Low Battery Cut
Out Hysteresis
Controls when the inverter turns off due to Hysteresis.
Low Battery Cut
Out Delay
Controls how long the inverter is allowed to operate at or below the Low Battery Cut
Out level before turning off due to a low battery voltage condition. The inverter will
turn off only after the Low Batt Cut Out level has been reached for this uninterrupted
period of time.
High Battery Cut
Out
High Battery Cut Out sets the maximum battery voltage at which the inverter will
operate. If the battery voltage exceeds this limit for more than 1 minute, the inverter
displays a fault message (F49) and shuts down. The inverter will not support AC
loads when in this condition. If a qualified AC source is present, the unit passes AC
through to the loads.
Search Mode Enables Search Mode when selected.
Search
Threshold
Search Watts sets the inverter’s search sensitivity when Search mode is enabled.
When a load larger than this setting is present, the inverter turns on.
Search Delay Search Delay sets the time between search pulses. When searching for loads, the
inverter/charger sends out search pulses to determine if a load is present. If the
inverter/charger finds a load above the Search Watts setting, the inverter comes on.
Max Discharge
Current
Lithium Ion Mode
only:
Specifies a percentage of battery current within which the
contactor will open in case of an overload.
Max Discharge
Interval
Specifies the interval in seconds between each verification of
the Max Discharge Current.
Inv Block Start Conext SW only: Sets the time to halt inverting.
Inv Block Stop Sets the time to resume inverting.