Conext Configuration Tool Manual

Device Configuration
3–8 975-0720-01-01
This manual is for use by qualified personnel only
Charger Configuration
Charger Configuration gives you options for configuring the inverter/charger to
operate from your battery bank.
Figure 3-7 Charger Configuration
Table 3-2 Charger Settings
Setting Description
Charger Enable Enables or disables the charger.
Maximum
Charge Rate
Sets the percentage of the maximum DC output current that is available to the
charger. Refer to the Owner’s Guide for your inverter to determine the maximum DC
output current for different models.
Charge Cycle Sets the charging method: 3Stage (Bulk, Absorption, Float) and 2StageNoFloat
(Bulk, Absorption, NoFloat).
ReCharge Volts Sets the battery voltage level at which a new charge cycle begins.
Charger Block
Start
Conext XW+ only: Sets the time to halt charging on AC1 (Grid). The AC2 (Gen)
port is unaffected by the Charger Block settings. The Charger
Block Start and Stop settings allow you to select when the
charger stops charging on AC1.
Conext SW only: Sets the time to halt charging.
To disable the Charger Block function, set Charger Block Start and Charger Block
Stop to the same time.