Conext Configuration Tool Manual

Device Configuration
3–10 975-0720-01-01
This manual is for use by qualified personnel only
AC Transfer Configuration
AC Transfer configures the voltage and frequency limits for AC line 1 (grid) and
AC line 2 (generator). These are the limits at which the inverter/charger considers
input voltage qualified—that is, suitable for charging batteries or powering loads.
If the input voltage is not qualified according to these settings, the inverter/
charger transfers from using AC input to inverting.
Bulk Termination
Voltage
Sets the minimum value of bulk voltage for a custom battery type.
Absorption
Voltage
Sets the absorption voltage for a custom battery type.
Absorption Time Sets the time spent in the Absorption stage, before transitioning to Float (3-Stage
charging) or NoFloat (2-Stage charging).
Float Voltage Sets the float voltage for a custom battery type.
Float Termination
Voltage
Sets the minimum value of float voltage for a custom battery type.
Battery
Temperature
Compensation
Battery temperature compensation for a custom battery type. This setting is the
reference that the battery temperature sensor uses to adjust the charging voltage
when the temperature falls above or below 25 °C.
Default Battery
Temperature
Selects the battery temperature charging compensation if a battery temperature
sensor is not installed. In the absence of a battery temperature sensor, the charger
uses one of three settings: “Cool” (5 °C), “Warm” (25 °C), or “Hot” (40 °C).
Table 3-3 Battery Configuration Menu
Figure 3-9 Inverter/Charger AC Transfer Configuration