Conext Configuration Tool Manual

Configuring Conext XW/XW+/SW Inverter/Chargers
975-0720-01-01 3–15
This manual is for use by qualified personnel only
Figure 3-12 Inverter/Charger Auxiliary Output Configuration
Table 3-7 Auxiliary Output Configuration Settings (Items in Gray Displayed When Auxiliary Output Mode
is set to “Automatic”)
Setting Description
Auxiliary
Output Mode
Sets the state of the Auxiliary Output. ManualOn or ManualOff allow manual control of the
Auxiliary Output. When set to Automatic, a trigger source can then be selected.
Active Output
Level
Sets the mode (polarity) of the auxiliary output. When triggered, the output can be active
high (12 VDC output turns on) or active low (output is high until the trigger turns it off).
Trigger Level Sets the voltage or temperature level (depending on the selected trigger source) at
which the auxiliary output is activated. If the selected Trigger Source is a Battery Voltage,
the range also varies according to the nominal battery voltage of your system.
Trigger Delay Sets a delay period between when the trigger occurs and when the auxiliary output is
activated.
Clear Level Sets the voltage or temperature level (depending on the selected trigger source) at
which the auxiliary output becomes inactive.
Clear Delay Sets a delay period between when the Clear Level setting occurs and when the auxiliary
output becomes inactive.
Trigger
Source
Selects the desired condition (Trigger Source) to activate the auxiliary output. The Trigger
Source options are Batt V Low, Batt V High, Batt Temp Low, Batt Temp High, Fault, Heat
Sink Temp High, State of Charge Low, and Time of Day.