Conext Configuration Tool Manual

Configuring Conext XW/XW+/SW Inverter/Chargers
975-0720-01-01 3–19
This manual is for use by qualified personnel only
Advanced Features Configuration
Advanced Features Configuration allows you to access the inverter/charger’s
advanced settings.
Figure 3-17 XW Inverter/Charger Advanced Features Configuration
Setting Description
Remote Power
Off
When an external switch has been connected to the Conext XW auxiliary port,
enabling this option will allow for the Conext XW to power off from the auxiliary port.
No Load Power
Save
When enabled, power save mode can reduce tare loss from the battery by reducing
output from 240 volts to 220 volts when the loads are less than 100 watts.
40 Second Sell
Delay
When enabled, there will be a 40 second delay before the system starts exporting
energy to the grid. This feature is useful when the battery voltage is not constant. It
also helps avoid power fluctuations during sell.
AC Coupling This function is enabled by default and should remain enabled except in cases where
the DC voltage level is allowed to have large variations and the AC line frequency
needs to remain constant.
Battery Energy
Balancing
This feature is intended for use with inverters drawing power from a single battery
bank. The Battery Balance function should be enabled when Conext XW+ units are
used in multi-cluster systems with multiple battery banks. When enabled, this feature
helps balance the power draw across multiple battery banks.
External Transfer
Switch
When enabled, the internal transfer switch is bypassed and the auxiliary output
controls an external transfer switch. For multi-unit 3 phase systems only. This feature
is mainly used in multi-cluster systems.
2hr Delay Into
Peak Load
Shaving
When enabled, PLS (Peak Load Shave) mode is delayed by 2 hours to allow the
MPPT solar charge controller to charge the battery bank first, then when the timer of 2
hours expires, the unit enters PLS mode for AC load support.