Saving and Restoring Configurations
Save Configuration allows you to save the current configuration of the inverter/
charger. Restore Configuration allows you to restore a previously saved
configuration from a file. See “Restoring a Configuration” on page 2–32 for further
details.
Configuring Conext MPPT 80 600 and Conext MPPT 60
150 Solar Charge Controllers
The following section describes how to configure Conext MPPT 80 600 and
Conext MPPT 60 150 Solar Charge Controllers.
To configure a Conext MPPT 80 600 or Conext MPPT 60 150 Solar Charge
Controller:
1. On the main screen, click the icon of the charge controller you want to
configure.
The charge controller’s Basic Status window opens.
2. In the Basic Status window, click Configure.
3. Click the settings category you want to configure.
The following settings categories are available on the Configure menu of the
MPPT 80 600 and MPPT 60 150 Solar Charge Controllers:
Multi-Unit Configuration
Charger Configuration
Battery Configuration
Solar Input Configuration
Auxiliary Output Configuration
Save Configuration
Restore Configuration
MPPT 80 600 only: Advanced Features
AC Transient
Over Voltage
When enabled, the inverter will stop exporting power to the grid when the grid
voltage exceeds 120% of nominal (as per HECO Standard).
GenSupp Plus Only enabled on a split-phase Conext XW. When enabled, this feature helps to
balance the generator input L1 and L2 phases under severe imbalanced loads on L1
and L2. This should only be enabled for generators below 5 kW.